Wsparcie Czujników Przemysłowych
Wsparcie Ochrony przed wybuchem
Niedostępne do zakupu
Niedostępne do zakupu

Inductive sensor NJ6-22-SN-G-Y30287

NJ6-22-SN-G-Y30287
  • 6 mm flush

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Pobierz pełną kartę katalogową w formie pliku PDF:


Dane techniczne  NJ6-22-SN-G-Y30287

General specifications
Switching functionNormally closed (NC)
Output typeNAMUR with safety function
Rated operating distance6 mm
Installationflush
Assured operating distance0 ... 4.86 mm
Reduction factor rAl 0.4
Reduction factor rCu 0.3
Reduction factor r304 0.85
Output type2-wire
Nominal ratings
Nominal voltage8 V
Operating voltage5 ... 25 V
Switching frequency0 ... 2000 Hz
Current consumption
Measuring plate not detectedmin. 3 mA
Measuring plate detected≤ 1 mA
Standard conformity
EMC in accordance withIEC / EN 60947-5-2:2004
StandardsDIN EN 60947-5-6 (NAMUR)
VDE 660 Part 209
Ambient conditions
Ambient temperature-40 ... 100 °C (-40 ... 212 °F)
Mechanical specifications
Core cross section0.75 mm2
Housing materialStainless steel
Sensing facePBT
Degree of protectionIP68
Dimensions
Length35 mm
Diameter21 mm
General information
Use in the hazardous areasee instruction manuals

Classifications

SystemClasscode
ECLASS 13.027274101
ECLASS 12.027274101
ECLASS 11.027272401
ECLASS 10.0.127272401
ECLASS 9.027272401
ECLASS 8.027272401
ECLASS 5.127272401
ETIM 9.0EC002714
ETIM 8.0EC002714
ETIM 7.0EC002714
ETIM 6.0EC002714
ETIM 5.0EC002714
UNSPSC 12.139121550

Details: NJ6-22-SN-G-Y30287

Product Documentation: NJ6-22-SN-G-Y30287

Language Selection:
Product informationJęzykTyp plikuRozmiar pliku
Installation conditionsENGPDF1054 KB

Design / Simulation: NJ6-22-SN-G-Y30287

Language Selection:
CADJęzykTyp plikuRozmiar pliku
CAD 3-D / CAD 3-DALLSTP54 KB

Approvals: NJ6-22-SN-G-Y30287

Language Selection:
CertificatesNr. certyfikatuJęzykTyp plikuRozmiar pliku
Canada USA CSA Ordinary Location1007121ALLPDF99 KB
Canada USA UL Ordinary LocationUL-US-L87056-11-41301991-3 / UL-CA-L87056-31-41301991-3ALLPDF1806 KB
exida Functional Safety AssessmentP+F 03/11-10 R015ALLPDF302 KB

Our amplify article gives interesting insights about the development of the new, modern portfolio of inductive proximity sensors from Pepperl+Fuchs. Get the whole story here! 

 

 

Knowledge Base for Inductive Sensors

The knowledge base for inductive sensors contains extensive expertise and supports you in the highly precise and smooth operation of the sensors in your machinery and plants.

VariKont z technologią aktywnego ekranowania

Czujniki indukcyjne VariKont z technologią aktywnego ekranowania zapewniają duże odległości przełączania, niezależnie od warunków instalacji i otaczającego materiału. Skorzystaj z prostszej konstrukcji sprzętu i obniżonych kosztów!

Indukcyjne czujniki bezpieczeństwa SIL 2 PL d

Dzięki temu, że indukcyjne czujniki bezpieczeństwa SIL 2/PL d nie mają martwej strefy, przesyłanie danych może odbywać się bez minimalnej odległości między czujnikiem a obiektem docelowym. Odkryj ofertę zoptymalizowaną pod kątem wymagających środowisk.