Wsparcie Czujników Przemysłowych
Wsparcie Ochrony przed wybuchem
Niedostępne do zakupu
Niedostępne do zakupu

SMART Current Driver HiC2031

HiC2031
  • 1-channel isolated barrier
  • 24 V DC supply (bus powered)
  • Current output up to 650 Ω load
  • Low power dissipation
  • Up to SIL 2 acc. to IEC/EN 61508

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Pobierz pełną kartę katalogową w formie pliku PDF:


Dane techniczne  HiC2031

General specifications
Signal typeAnalog output
Functional safety related parameters
Safety Integrity Level (SIL)SIL 2
Supply
ConnectionSL1: 1a(-), 1b(-); 2a(+), 2b(+)
Rated voltage19 ... 30 V DC bus powered via Termination Board
Ripple≤ 10 %
Rated current≤ 30 mA
Power dissipation≤ 600 mW
Power consumption≤ 700 mW
Input
Connection sidecontrol side
ConnectionSL1: 8a(+), 7a(-)
Input signal4 ... 20 mA limited to approx. 30 mA
Input voltagedepending on switch configuration
open loop voltage of the control system < 23 V
open loop voltage of the control system < 27 V
Voltage dropdepending on switch configuration
open loop voltage of the control system < 23 V: approx. 6 V at 20 mA
open loop voltage of the control system < 27 V: approx. 10 V at 20 mA
Input resistance> 100 kΩ, with field wiring open
Output
Connection sidefield side
ConnectionSL2: 5a(+), 5b(-)
Voltage≥ 13 V at 20 mA
Current4 ... 20 mA
Load0 ... 650 Ω
Ripple20 mV rms
Transfer characteristics
Deviationat 20 °C (68 °F), 0/4 ... 20 mA
≤ ± 0.1 % incl. non-linearity and hysteresis
Influence of ambient temperature< 2 µA/K (0 ... 60 °C (32 ... 140 °F)); < 4 µA/K (-20 ... 0 °C (-4 ... 32 °F))
Frequency rangefield side into the control side: bandwidth with 0.5 Vpp signal 0 ... 3 kHz (-3 dB)
control side into the field side: bandwidth with 1 mApp signal 0 ... 3 kHz (-3 dB)
Rise time10 to 90 % ≤ 100 ms
Galvanic isolation
Input/Outputsafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Input/power supplyfunctional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
Output/power supplysafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Indicators/settings
Display elementsLED
Control elementsDIP switch
Factory settinginput: max. input voltage 23 V
Configurationvia DIP switches
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Conformity
Electromagnetic compatibilityNE 21:2006
For further information see system description.
Degree of protectionIEC 60529:2001
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protectionIP20
Massapprox. 100 g
Dimensions12.5 x 106 x 128 mm (0.5 x 4.2 x 5.1 inch)
Height128 mm
Width12.5 mm
Length106 mm
Mountingon termination board
Codingpin 1 and 3 trimmed
For further information see system description.
Data for application in connection with hazardous areas
EU-type examination certificateCESI 06 ATEX 017
MarkingEx-Hexagon II (1)G [Ex ia Ga] IIC
Ex-Hexagon II (1)D [Ex ia Da] IIIC
Ex-Hexagon I (M1) [Ex ia Ma] I
OutputEx ia
Supply
Maximum safe voltage253 V AC (Attention! Um is no rated voltage.)
EquipmentSL2: 5a(+), 5b(-)
Voltage25.2 V
Current100 mA
Power630 mW
Internal capacitance5.7 nF
Internal inductancenegligible
CertificateKIWA 15 ATEX 0035 X
MarkingEx-Hexagon II 3G Ex ec IIC T4 Gc
Directive conformity
Directive 2014/34/EUEN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-7:2015+A1:2018 , EN 50303:2000
International approvals
FM approval
Control drawing16-534FM-12 (cFMus)
IECEx approval
IECEx certificateIECEx CES 06.0002
IECEx KIWA 15.0017X
IECEx marking[Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I
Ex ec IIC T4 Gc
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027210120
ECLASS 12.027210120
ECLASS 11.027210120
ECLASS 10.0.127210120
ECLASS 9.027210120
ECLASS 8.027210120
ECLASS 5.127210120
ETIM 9.0EC002653
ETIM 8.0EC002653
ETIM 7.0EC002653
ETIM 6.0EC002653
ETIM 5.0EC001485
UNSPSC 12.132101514

Details: HiC2031

Function

This isolated barrier is used for intrinsic safety applications.

It repeats the input signal from a control system to drive HART I/P converters, valve actuators, and displays located in a hazardous area.

Digital signals are superimposed on the analog values at the field side or control side and are transferred bi-directionally.

An open field circuit presents a high impedance to the control side to allow alarm conditions to be monitored by the control system.

This device mounts on a HiC termination board.

Product Documentation: HiC2031

Language Selection:
Safety and Security DocumentationJęzykTyp plikuRozmiar pliku
Instrukcja obsługiPOLPDF166 KB
ManualENGPDF360 KB
Manuals
System ManualENGPDF5438 KB

Design / Simulation: HiC2031

Language Selection:
CADJęzykTyp plikuRozmiar pliku
CAD 2-D / CAD 2-DALLZIP16364 KB
CAE
EPLAN macros H-System devices (EMA) / EPLAN-Makros Geräte H-System (EMA)ALLZIP3536 KB

Approvals: HiC2031

Language Selection:
CertificatesNr. certyfikatuJęzykTyp plikuRozmiar pliku
Brasil TUV Rheinland BrazilTÜV 16.0820ALLPDF1160 KB
CESI IECEx Certificate of ConformityIECEx CES 06.0002XALLLINK---
Canada FMFM19CA0065XALLPDF374 KB
Europe CESI ATEX Category (1) D ATEX Category (M1) ATEX Category (1) GCESI 06 ATEX 017ALLPDF788 KB
Europe KIWA ATEX Category 3 GKIWA 15 ATEX 0035XALLPDF113 KB
KIWA IECEx Certificate of Conformity Zone 2IECEx KIWA 15.0017XALLLINK---
Korea KOSHA23-AV4BO-0172XALLPDF542 KB
Korea KOSHA15-AV4BO-0594ALLPDF661 KB
South Africa MASCMASC MS/18-0089XALLPDF817 KB
USA FMFM19US0122XALLPDF346 KB
United Kingdom CML UKEX Category (1) D UKEX Category (1) G UKEX Category (M1)CML 21UKEX2939ALLPDF195 KB
Control Drawings
Control drawing FM / Control drawing FM   ALLPDF112 KB
Safety Products Selector

Choose from various selection criteria like safety integrity level, performance level, device function, and signal type and find the SIL/PL assessed device that you are looking for.