Wsparcie Czujników Przemysłowych
Wsparcie Ochrony przed wybuchem

Surge Protection Barrier M-LB-Ex-2112.SP

M-LB-Ex-2112.SP
  • Surge protection barrier for 2 signal lines
  • Nominal voltage 1 V DC
  • Surge protection barrier for non-grounded signal lines
  • Max. surge current (8/20 µs) 20 kA
  • Connection via spring terminals with push-in connection technology
  • DIN rail mountable
  • Up to SIL 3 acc. to IEC/EN 61508

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Dane techniczne  M-LB-Ex-2112.SP

General specifications
Number of protected signal lines2
Topologynon-grounded
Functional safety related parameters
Safety Integrity Level (SIL)SIL 3
Electrical specifications
Connectionprotected area: terminals 4, 5
unprotected area: terminals 2, 3
shielding/grounding: terminal 1 (optional)
Rated current500 mA , restrictions see derating tables
UL : 400 mA , restrictions see control drawing
Leakage current< 5 µA at 1 V and 25 °C (77 °F) , line-line
Nominal voltage1 V DC
Maximum continuous operating voltage6 V DC
Series resistance≤ 3 Ω per line
Impulse rating1 kV/0.5 kA (category C1)
10 kV/5 kA (category C2)
1 kA (category D1)
Impulse discharge current (10/350 µs)1 kA per line (2x)
Nominal discharge current (8/20 µs)5 kA per line (10x)
Total discharge current (8/20 µs)20 kA (1x) , overstressed fault mode 3 acc. to IEC 61643-21
Voltage protection levelmax. 12 V line-line for nominal discharge current In
max. 1400 V line-earth for nominal discharge current In
Impulse reset time< 500 ms
Insertion loss≤ 3 dB at 0 ... 400 kHz in 100 Ω system
Conformity
Electromagnetic compatibilityEN 61326-3-1:2017
Degree of protectionIEC 60529:2013
Functional safetyIEC/EN 61508:2010
Surge protective devices for low voltageIEC 61643-21:2000+A1:2008+A2:2012
Ambient conditions
Ambient temperature-40 ... 80 °C (-40 ... 176 °F)
Observe the temperature range limited by derating, see section derating.
Storage temperature-40 ... 85 °C (-40 ... 185 °F)
Relative humiditymax. 95 % , without condensation
Corrosion resistanceacc. to ISA-S71.04, severity level G3
Mechanical specifications
Degree of protectionIP20 , after mounting of the insulation spacer
Connectionspring terminals , max. core cross section 1 x 2.5 mm2
MaterialPolyamide (PA)
Massapprox. 32 g
Dimensions6.2 x 93 x 72.4 mm (0.24 x 3.7 x 2.8 inch) (W x H x D)
Height93 mm
Width6.2 mm
Depth72.4 mm
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
EU-type examination certificateKIWA 19 ATEX 0003 X
MarkingEx-Hexagon II 2(1)G Ex ia [ia Ga] IIC T6...T4 Gb
Ex-Hexagon II (1)D [Ex ia Da] IIIC
Ex-Hexagon I (M1) [Ex ia Ma] I
Temperature classT6, T5 or T4 , restrictions see derating tables
Voltage6 V
Current500 mA , restrictions see derating tables
Internal capacitancenegligible
Internal inductance20 µH
Directive conformity
Directive 2014/34/EUEN IEC 60079-0:2018+AC:2020 , EN 60079-11:2012
International approvals
UL approvalE501704
E501881
Control drawing116-0479
Current400 mA , restrictions see control drawing
Breakdown voltage6 ... 12 V line-line at 100 V/s acc. to UL 497B
< 1000 V at 100 V/µs acc. to UL 497B
IECEx approval
IECEx certificateIECEx KIWA 19.0003X
IECEx markingEx ia [ia Ga] IIC T6...T4 Gb
[Ex ia Da] IIIC
[Ex ia Ma] I
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027171202
ECLASS 12.027171202
ECLASS 11.027130805
ECLASS 10.0.127130805
ECLASS 9.027130805
ECLASS 8.027130805
ECLASS 5.127130801
ETIM 9.0EC000941
ETIM 8.0EC000941
ETIM 7.0EC000941
ETIM 6.0EC000941
ETIM 5.0EC000941
UNSPSC 12.139121610

Details: M-LB-Ex-2112.SP

The device limits induced transients of different causes, e. g. lightning or switching operations. The limitation is achieved by diverting the current to earth and limiting the signal loop voltage during the duration of the overvoltage pulse.

The device is used for intrinsic safety applications.

The device is HART transparent.

The device is mounted on a 35 mm DIN mounting rail according to EN 60715.

Datasheet: M-LB-Ex-2112.SP

DatasheetTyp plikuRozmiar pliku
Datasheet M-LB-Ex-2112.SPPDF1416 KB
Fiche de données M-LB-Ex-2112.SPPDF1426 KB
Datenblatt M-LB-Ex-2112.SPPDF1420 KB
Datasheet M-LB-Ex-2112.SPPDF1487 KB
Hoja de datos M-LB-Ex-2112.SPPDF1427 KB

Documents: M-LB-Ex-2112.SP

ManualsTyp plikuRozmiar pliku
ManualPDF3280 KB
HandbuchPDF3290 KB
Instruction manuals
ИнструкцииPDF166 KB
Instruction manual / BetriebsanleitungPDF321 KB
Návod k poużitíPDF160 KB
Instruktions manualPDF159 KB
Instruction manualPDF164 KB
KasutusjuhendPDF155 KB
KäyttöohjePDF154 KB
Manuel d'instructionsPDF162 KB
BetriebsanleitungPDF165 KB
Οδηγίες χρήσηςPDF169 KB
HandleidingPDF160 KB
Instruction manual / BetriebsanleitungPDF158 KB
Használati útmutatóPDF161 KB
Manuale di istruzioniPDF159 KB
Lietošanas pamācībaPDF158 KB
Instrukciju vadovasPDF160 KB
Instrukcja obsługiPDF160 KB
Manual de instruçõesPDF160 KB
Manual de utilizarePDF159 KB
Návod na poużitiePDF160 KB
Navodila za uporaboPDF157 KB
Manual de instruccionesPDF160 KB
ManualPDF157 KB
Documents
Functional Safety ManualPDF602 KB
Handbuch funktionale SicherheitPDF612 KB

Approvals+Certificates: M-LB-Ex-2112.SP

CertificatesTyp plikuRozmiar pliku
Canada, USA UL Hazardous LocationPDF421 KB
China SITIIAS CCC Ex CertificatePDF1133 KB
Europe KIWA I (M1) II 2(1)G ATEX II (1) DPDF116 KB
India PESO (India) CCOEPDF459 KB
Worldwide CSA IECEx Certificate of ConformityLINK---
Worldwide ÖVE (Austria) Surge Protective DevicePDF352 KB
Control Drawings
Control drawing CSA / Control drawing CSAPDF334 KB
Declaration of Conformity
EU Declaration of Conformity (P+F)PDF191 KB
EU Declaration of Conformity (P+F)PDF187 KB
EU Declaration of Conformity (P+F)PDF185 KB
EU Declaration of Conformity (P+F)PDF187 KB
EU Declaration of Conformity (P+F)PDF184 KB
EU Declaration of Conformity (P+F)PDF184 KB
EU Declaration of Conformity (P+F)PDF185 KB
EU-Konformitäterklärung (P+F)PDF187 KB
EU Declaration of Conformity (P+F)PDF191 KB
EU Declaration of Conformity (P+F)PDF184 KB
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)PDF185 KB
EU Declaration of Conformity (P+F)PDF188 KB
EU Declaration of Conformity (P+F)PDF184 KB
EU Declaration of Conformity (P+F)PDF185 KB
EU Declaration of Conformity (P+F)PDF187 KB
EU Declaration of Conformity (P+F)PDF187 KB
EU Declaration of Conformity (P+F)PDF186 KB
EU Declaration of Conformity (P+F)PDF186 KB
EU Declaration of Conformity (P+F)PDF188 KB
EU Declaration of Conformity (P+F)PDF185 KB
EU Declaration of Conformity (P+F)PDF185 KB
EU Declaration of Conformity (P+F)PDF185 KB
EU Declaration of Conformity (P+F)PDF187 KB

Produkty powiązane: M-LB-Ex-2112.SP

Matching System Components
Accessory Surge Protection, For equipotential bonding via DIN mounting railpa
Accessories
For surge protection system M-LB-2000, Color black, DIN rail mountablepa
Safety Products Selector

Choose from various selection criteria like safety integrity level, performance level, device function, and signal type and find the SIL/PL assessed device that you are looking for.

„Centrum bezpieczeństwa funkcjonalnego” firmy Pepperl+Fuchs

Kilkaset produktów z oceną kategorii SIL/PL oraz bezpłatne narzędzia i broszury w jednym miejscu — „Centrum bezpieczeństwa funkcjonalnego” to Twój punkt wyjścia przy wdrażaniu funkcji bezpieczeństwa.

Wyszukiwarka produktów związanych z bezpieczeństwem dla produktów z określonym poziomem SIL/PL

Szukasz konkretnego produktu z określonym poziomem SIL/PL? Nasze narzędzie wyszukiwania przedstawia przegląd urządzeń z określonym poziomem bezpieczeństwa, w tym poziom nienaruszalności bezpieczeństwa (Safety Integrity Level — SIL) oraz poziom zapewnienia bezpieczeństwa (Performance Level — PL) — wypróbuj je!